                酒店电气系统的方案设计

                文章出处:年之轮室内设计顾问机构 发表时间:2016-08-25 15:40 


                用电负荷分级及容量:

                    根据国家相关规范及酒店管理公司的设计要求,本工程的一级负荷为:消防设备(包括消防泵、喷淋泵、正压及排烟风机等)、消防控制中心、电梯、应急和疏散指示照明、弱电总机房、计算机房、生活水泵、客房用电、酒店大堂用电、主要厨房等;二级负荷为:空调主机、特色餐厅、洗衣房、室外照明等;除此之外的均为三级负荷。总设备容量:11036kW;总计算负荷:5780.1kVA;总变压器安装容量:8545KVA;变压器平均负荷率:67.6%

                供配电系统:

                    五星级酒店供电要求较高,存在大量的一、二级负荷,故本系统引来两路独立的10kV专线电源,电源以电缆埋地型式进入工程内的变电所。10kV配电所的接线形式为单母线分段,设母线联络开关,两路10kV电源同时工作、互为备用,其中一路停电,另一路均能承担本工程的全部负荷,母线联络开关为自投;10KV配电至各变电所变压器采用放射式交叉配电。